MEASURESAFE 36

SPECIFICATIONS

Mains Voltage Accuracy:

+-0.5%

 

Operational Temperature:

0°C to +60°C

Tripping Current Accuracy:

+0.5mA

 

Storage Temperature:

-20°C to +70°C

Trip Time Accuracy:

0-400mS ± 1mS

 

Dimensions H x W x L:

195 x 100 x 39mm

Loading Slope Phase angle

Selectable 0, 90, 180, 270 Degrees

 

Weight:

450g

Result storage

Model dependant

0 results Basic unit

2000 Results

4000 Results

 

RCD type Selection

Type I – 10mA

Type II – 30mA

Type Custom selectable 1-50mA

Type AFCI

RTC

The unit has a built in battery backup real time clock for time and date stamping of test results

 

Downloading

The results can be down loaded using a simple serial terminal or the optional software interface.

Test Leakage Current Range :

2mA to 50mA in 0.5mA steps

 

Power inlet

IEC socket

Internal fuse

1A 250Vac

 

Approvals

C-tick

Operating Voltage:

85-265VAC 50-60 Hz

 

Service & calibration:

By manufacturer only

Test Time:

90sec maximum depending upon trip current of the RCD.

 

Fault Reports:

Incorrect mains wiring (active and neutral swapped), no earth connected, RCD fails to trip.

Test Current:

Incremented test sequence from 0mA until RCD trips or fails.

 

Calibration Requirement:

Every year or approximately 4000 RCD tests (requires battery replacement & re-calibration)

Display

2 line LCD display showing mains voltage, RCD trip time, RCD trip current and any RCD faults.

User selectable display time.

 

Other Requirements:

Warranty Void and Test Results not guaranteed if the case tamper seal damaged or removed.

Power Supply:

Powers up from mains source.  Serviceable internal battery with a 2000 RCD test life.

 

Optional Extras:

Adaptor with Alligator leads and probes for testing RCD’s in meter boxes or directly on wiring.

 

Download User Manuall here.