SPECIFICATIONS
|
|
Mains
Voltage Accuracy:
|
+-0.5%
|
|
Operational
Temperature:
|
0°C to +60°C
|
|
Tripping
Current Accuracy:
|
+0.5mA
|
|
Storage
Temperature:
|
-20°C to +70°C
|
|
Trip
Time Accuracy:
|
0-400mS
± 1mS
|
|
Dimensions H x W x L:
|
195
x 100 x 39mm
|
|
Loading
Slope Phase angle
|
Selectable
0, 90, 180, 270 Degrees
|
|
Weight:
|
450g
|
|
Result
storage
|
Model
dependant
0
results Basic unit
2000
Results
4000
Results
|
|
RCD
type Selection
|
Type I – 10mA
Type II – 30mA
Type
Custom selectable 1-50mA
Type AFCI
|
|
RTC
|
The
unit has a built in battery backup real time clock for time and date
stamping of test results
|
|
Downloading
|
The
results can be down loaded using a simple serial terminal or the
optional software interface.
|
|
Test
Leakage
Current
Range
:
|
2mA
to 50mA in 0.5mA steps
|
|
Power
inlet
|
IEC
socket
|
|
Internal
fuse
|
1A
250Vac
|
|
Approvals
|
C-tick
|
|
Operating
Voltage:
|
85-265VAC
50-60 Hz
|
|
Service
& calibration:
|
By
manufacturer only
|
|
Test
Time:
|
90sec
maximum depending upon trip current of the RCD.
|
|
Fault
Reports:
|
Incorrect
mains wiring (active and neutral swapped), no earth connected, RCD
fails to trip.
|
|
Test
Current:
|
Incremented
test sequence from 0mA until RCD trips or fails.
|
|
Calibration
Requirement:
|
Every
year or approximately 4000 RCD tests (requires battery replacement
& re-calibration)
|
|
Display
|
2
line LCD display showing mains voltage, RCD trip time, RCD trip
current and any RCD faults.
User
selectable display time.
|
|
Other
Requirements:
|
Warranty
Void and Test Results not guaranteed if the case tamper seal damaged
or removed.
|
|
Power
Supply:
|
Powers
up from mains source. Serviceable
internal battery with a 2000 RCD test life.
|
|
Optional
Extras:
|
Adaptor
with Alligator leads and probes for testing RCD’s in meter boxes
or directly on wiring.
|