|
Testing RCD"s with an
isolation transformer
When conducting testing on RCD's if the RCD is being tested on a
protected line there is the potential to trip the RCD at the main switch
board. This is not desirable. The easiest way to do this is to use an
isolation transformer, however the transformer needs to be modified to
ensure that the isolation transformer does not interfere with the normal
testing.
The purpose of an isolation transformer is to
electrically isolate the mains while maintaining a 1:1 voltage ratio. As
simple diagram below shows an isolation transformer.
 
Normal Isolation transformer
Modified for RCD testing
As can be seen in the simple diagram
the Isolated secondary is completely disconnected from the Primary.
As a result of the isolation transformer there will be no imbalance in the
primary current and as such the RCD on the primary side will not trip.
In order to test RCD or to have
RCD’s function correctly after the isolation transformer the Neutral
Isolated must be connected to the Earth line. Other wise there is no way the
RCD can function correctly and any subsequent testing will fail or give
misleading results.
|